CUPBOARD STORE (single)(make up partitions to 30 minutes resistance)

CUPBOARD / STORE (single)(make up partitions to 30 minutes resistance)

Make up the partitions within the cupboard/store situated # specify position #. to a standard of fire resistance of at least 30 minutes. The standard of construction to be in accordance with Appendix I to this schedule. Junctions with adjacent structural elements, including soffit of staircase, shall be constructed so that the structure maintains its fire integrity in the event of a fire, and is imperforate and sealed against the passage of the products of combustion on completion. Fill any gaps around cables and pipes with intumescent paste. Provide and fit a suitable lock to the door (which is to be kept locked at all times when not in use). The cupboard to be fitted with a solid door of at least 44mm in thickness, fitted with 10-15mm wide intumescent seals to jambs and top edge. The gap between door edges and frame should not exceed 4mm. The door to be labelled “Fire door keep locked shut”.


CUPBOARD STORE (single)(make up partitions to 30 minutes resistance)